"Maximum Rating or Setting for Motor Branch Circuits"
Motor Branch - Circuit Protective Devices
Maximum Rating or Setting
|
||||
|---|---|---|---|---|
| Type of Motor | Nontime Delay Fuse** |
Dual
Element (Time Delay) Fuse** |
Instantaneous Trip Breaker |
Inverse
Time Breaker |
| Single Phase AC polyphase other than wound rotor Squirrel Cage |
300 | 175 | 800 | 250 |
| Other than Design E | 300 | 175 | 800 | 250 |
| Design E | 300 | 175 | 1100 | 250 |
| Synchronous | 300 | 175 | 800 | 250 |
| Wound Rotor | 150 | 150 | 800 | 150 |
| Direct-Current (constant voltage) |
150 | 150 | 250 | 150 |
If there is anything you would like to add or if you have any comments please feel free to email E.T.E. at http://www.elec-toolbox.com/email.htm