Correct! B. Section 210-8(b) {Other than dwelling units:}states all 125 volt, single phase, 15 and 20 amp receptacles installed in the locations specified below shall have GFCI protection for personnel.

(1) Bathrooms
(2) Rooftops

Exceptions: Receptacles that are not readily that are not readily accessible and are supplied from a dedicated branch circuit for electric snow-melting or deicing equipment shall be permitted to be installed in accordance with the applicable provisions of article 426.