Correct!  A. Section 110-14(c)(1) states terminations provisions of equipment for circuits rated 100 amps or less, or marked for Nos. 14 through 1 conductors, shall be used for the following:

(a) Conductors rated 60° C , or
(b) Conductors with higher temperature ratings, provided the ampacity of such conductors is determined based on the 60°  C ampacity of the conductor size used , or
(c) Conductors with a higher temperature ratings if the equipment is listed and identified for use with such conductors, or
(d) For motors with a design letters B, C, D, or E, conductors having an insulation rating of 75°  C or higher shall be permitted to be used provided the ampacity of such conductors does not exceed the 75°  C ampacity.