Correct! B. Section 110-26 (f)(1)(a) states that 6 feet above the equipment or to the structural ceiling, whichever is lower shall be dedicated for electrical installation. No piping, ducts, or equipment foreign to the electrical installation shall be located in this zone.
Exception: Equipment that is isolated from the foreign equipment by height or physical enclosures or covers that will afford adequate mechanical protection from vehicular traffic or accidental contact by unauthorized personnel or that complies with (b), shall be permitted in areas that do not have the dedicated space described in this rule.
(b) Foreign Systems: The space equal to the width and depth of the equipment shall be kept clear of foreign systems unless protection is provided to avoid damage from condensation, leaks, or breaks in such foreign systems. This zone shall extend from the top of the electrical equipment to the structural ceiling.